VlamShield SignetVlamShield
← Back to SHEET

VlamShield / SHEET

Technical product information

SHEET Mineral protection and load-spreading board

Fibre-reinforced, cement-bound board for flat roofs with PV and technical installations. Preferred position: above thermal insulation and below the waterproofing membrane.

16.09.2026 · 0.2

White mineral SHEET boards with a visible fibre structure along their edges
Nominal thickness
10 mm
Board size
1,500 × 1,250 mm
Mass per area
10 kg/m²
Mass per board
≈ 18.75 kg

Position in the roof

  1. 01PV / rooftop installation
  2. 02Waterproofing membrane
  3. 03SHEET · mineral board
  4. 04Thermal insulation
  5. 05Vapour control layer
  6. 06Load-bearing structure

Schematic sequence from top to bottom. Fixings and junction details are project-specific.

Product and function

SHEET combines a cement-bound mineral matrix with fibre reinforcement. The factory-cured board is intended as an additional protective and load-spreading layer within the roof build-up.

It can spread local loads from support points, maintenance traffic and technical equipment over a larger insulation area. The achievable distribution depends on board properties, support geometry, joints, insulation and load duration; it does not increase the roof structure’s available load capacity.

Technical product data

PropertyValue
ProductVlamShield SHEET
MaterialCement-bound, fibre-reinforced mineral board
Nominal thickness10 mm
Standard board size1,500 × 1,250 mm
Area per board1.875 m²
Mass per area10 kg/m²
Mass per board18.75 kg, calculated
Preferred positionAbove thermal insulation, below roof waterproofing
ApplicationFlat roofs with PV and technical equipment
Permissible point load / system load capacityBuild-up dependent; no approved tabulated value yet
Reaction to fire / fire resistanceOnly with the corresponding product or system evidence
Dimensional and mass tolerancesTo be established

Calculation: 1.50 m × 1.25 m = 1.875 m²; 1.875 m² × 10 kg/m² = 18.75 kg per board. Dimensions and mass per area are nominal values. Cutting waste and other roof layers are not included.

Loads beneath photovoltaic systems

PV mounting structures, ballast, maintenance traffic and technical equipment impose different loads. Assessment of SHEET covers both added distributed weight and local loads, including compression of the insulation.

Covering 100 m² adds approximately 1,000 kg of board mass by calculation. PV, mounting structure, ballast and other layers are additional. Total loads and installation-stage loads must be checked against the roof’s available capacity.

The board does not replace the load-bearing structure or structural verification. Its mass per area does not establish general approval for arbitrary PV support points or ballast.

Insulation and waterproofing combinations

PIR, EPS, mineral wool, wood-fibre insulation and cellular glass are considered for system selection. This list does not approve every manufacturer or strength grade.

Insulation compression and long-term deformation, loaded area, board joints and edges are critical. The membrane, adhesives, separation layers and fixings must suit the complete build-up. Each project combination is coordinated with its supporting documentation.

Mineral protection and fire performance

SHEET forms an additional mineral layer between insulation and waterproofing. Thermal protection also depends on joints, thickness, heat transfer and the complete roof build-up.

Mineral composition alone establishes neither a reaction-to-fire class, fire resistance nor insurer acceptance. Specific classifications will be added with the corresponding test report and field of application.

Handling and installation sequence

1. Coordinate the build-up and loads

Identify insulation, proposed membrane, support points, drainage and spare load capacity. The substrate and insulation must provide suitable continuous support.

2. Handle and lay the boards

Account for board size, approximately 18.75 kg per board and wind conditions during transport and installation. Coordinate laying sequence and cutting with the roof plan. Store boards dry and protected.

3. Plan joints, junctions and wind restraint

Specify joints, edges, penetrations, fixings and any adhesive bonding in the installation plan. This data sheet does not provide universal fixing spacings.

4. Install the waterproofing

The subsequent membrane provides the waterproofing function. Protect open work areas from moisture and plan continuous junctions and outlets. The installation instructions for the selected configuration govern the work.

Moisture and weather exposure

The standard application is below the waterproofing membrane. Permanent exposure to weather is not included and requires explicit approval for the relevant system.

SHEET does not replace roof waterproofing. Repeated wetting, wet–dry cycles and construction moisture must be considered in material selection, storage and construction sequencing.

Testing and system assessment

Technical assessment covers fire performance, point loads and load distribution with the intended insulation, as well as the secured roof build-up under wind loading.

Permissible loads must be assigned to the particular combination of board, insulation, support and fixing. No load limits, wind ratings or certifications are stated here without applicable results. International or insurance-related requirements, including FM, require their own supporting evidence.

Project information and contact

For project coordination, provide roof area and plan, spare load capacity, insulation type and thickness, proposed membrane, PV support points and ballast, and the installation schedule.

VlamShield · SHEET
info@vlamshield.nl

This data sheet contains technical product information. Binding configurations, properties and installation details are assigned to the relevant product and system documentation.

Current version and project-specific documentation: vlamshield.nl

Project enquiry

Send your roof build-up. Discuss the material choice.

A few photos and the roof area are enough to start. You receive a project proposal with the specific configuration, the supporting documentation and the open points we agree with you.

Illustration of the digital AI project adviser
AI assistant

Your roof. Your questions.

Hello! I am VlamShield’s AI project adviser. What would you like to know about your roofing project?

What are you planning?

or drop them here

    JPG, PNG, WebP, PDF or TXT · up to 3 files, 10 MB each, 15 MB total · up to 6 images/PDF pages.

    Attachments are sent to OpenAI only with your question and stay selected for follow-up questions. We do not store them permanently or automatically attach them to project enquiries.

    AI guidance, not technical approval. Text and attachments are sent to OpenAI. Remove personal and confidential details first. Privacy